Abstract:Recent advancements in high-precision measurement devices,such as mirco-phase measurement
unit(μPMU),offer technical support for regional protection schemes. However,deploying μPMU across all
network nodes remains impractical due to economic and practical constraints. Therefore,under low-resistance
grounded distribution network conditions,a node zero-sequence voltage estimation method was proposed under
limited μPMU deployment. Furthermore,this method was applied to estimate unknown zero-sequence voltages at
nodes within fault regions,enabling calculation of the relative position coefficient α between fault points and
regional lines. Based on α,a fault line identification criterion was established,forming a regional protection
scheme. Finally,simulation results validate the effectiveness of the proposed method.
Key words:distribution network regional protection;zero-sequence voltage estimation;limited measurement;inverter interfaced distributed generator (DG)
Format Citation:李娟,姜云龙,朱睿,等. 有限量测下基于零序电压推算的有源配电网区域保护方法[J].电气传动,2026,56(08):49-58. LI Juan,JIANG Yunlong,ZHU Rui,et al. Zero-sequence voltage estimation based regional protection method for active distribution networks under limited measurement [J].Electric Drive, 2026,56(08): 49-58