Zero-sequence Voltage Estimation Based Regional Protection Method for Active Distribution Networks Under Limited Measurement

Release date:2026-08-20  Number of views:136   Amount of downloads:390   DOI:10.19457/j.1001-2095.dqcd26635

        Abstract:Recent advancements in high-precision measurement devices,such as mirco-phase measurement

unit(μPMU),offer technical support for regional protection schemes. However,deploying μPMU across all

network nodes remains impractical due to economic and practical constraints. Therefore,under low-resistance

grounded distribution network conditions,a node zero-sequence voltage estimation method was proposed under

limited μPMU deployment. Furthermore,this method was applied to estimate unknown zero-sequence voltages at

nodes within fault regions,enabling calculation of the relative position coefficient α between fault points and

regional lines. Based on α,a fault line identification criterion was established,forming a regional protection

scheme. Finally,simulation results validate the effectiveness of the proposed method.


        Key words:distribution network regional protection;zero-sequence voltage estimation;limited measurement;inverter interfaced distributed generator (DG)