Abstract:Due to the wide control bandwidth of the shunt active power filter(SAPF),the resonance problem
of the LCL output filter has become a key problem of the SAPF. To solve the resonance problem of the LCL filter,a
novel damping method based on active damping circuit was proposed to achieve the damping effect without
affecting the SAPF control. The proposed method was based on an auxiliary converter connected in series with the
capacitor branch of LCL filter. In the auxiliary converter,the resonant current was detected and injected inversely as
the reference signal of the converter,to achieve the damping effect on the resonant current. The stability of the
proposed method was carried out through the frequency response analysis,and compared with the traditional
method,which proved the theoretical feasibility of the proposed method. Finally,the effectiveness of the proposed
method was verified by the experimental results,and it has better switching harmonic suppression effect compared
with the traditional passive damping method.