Manuscript details
Current location:Home >Manuscript details
Release date:2024-03-20 Number of views:657 Amount of downloads:537 DOI:10.19457/j.1001-2095.dqcd24621
Abstract:The circulating current of metal sheath in high voltage cable is the superposition of induced current
component and leakage current component. At present,the calculation of induced current component is relatively
mature,but the calculation of leakage current component is insufficient,which affects the final circulating current
calculation result and the related fault diagnosis effect. For this reason,a calculation method for leakage current
component of sheath circulating current in high voltage cable was proposed. Based on the π-type equivalent circuit
of "core—sheath",an equivalent circuit for solving leakage current component of sheath circulating current was
established,which take into account the shunting effect of leakage current and circulating current generated by
leakage current of cable core. The final leakage current component was obtained based on the iterative method. A
cable model with a linear arrangement was built using ATP-EMTP software. The results show that the relative
deviation between calculation result and simulation value of this method is within 2% under different length
combinations and load currents,compared with existing method,the accuracy is greatly improved. This method
can better explain the reason of excessive circulating current at light load,and has a certain reference for the
generation of sample data for fault diagnosis of cross-connected systems.
Key words:high voltage cable;cross-bonding;circulating current of sheath;induced current component;
leakage current component
Classification
Copyright Tianjin Electric Research Institute Co., Ltd Jin ICP Bei No. 07001287 Powered by Handynasty
Online illegal and bad information reporting hotline (Hedong District):022-84376127
Report Mailbox:wangzheng@tried.com.cn