Abstract: The penetration rate of renewable energy in the island AC microgrid was relatively high,and its
system inertia was relatively low. The primary frequency regulation during island operation mainly relies on
equipment such as diesel engines and energy storage. Using the fast adjustment characteristics of energy storage
and static var generator(SVG),a frequency coordinated control strategy for island microgrid based on voltage
adjustment was proposed. When the frequency of the island microgrid fluctuates,the load node voltage was
changed through the coordinated control of energy storage and SVG,and the static characteristics of the load
voltage was used to quickly adjust the system frequency. In this control strategy,both energy storage and SVG
adopt droop control,no remote communication was required,and only load node voltage and frequency signals
need to be detected. This control can reduce the configuration of the energy storage capacity of the microgrid and
improve system stability. Through DIgSILENT/PowerFactory simulation research,the control strategy was verified.
Key words: microgrid;droop control;SVG control;primary frequency regulation