Abstract: There are parameter identification errors in the process of distribution network synchronous
measurement configuration. The optimal configuration method of distribution network synchronous measurement
device based on parameter identification accuracy was studied. Based on the measurement data of the synchronous
measurement device,the branch parameters of the whole distribution network were estimated step by step from the end node of the distribution network,and the line parameters at different times in the operation process of the
distribution network were determined by using the least square algorithm. According to the sensitivity of the
measurement noise,the dispersion index was determined,and the internal parameters of the synchronous
measurement device configuration algorithm were constructed with the comprehensive optimization of the
identification accuracy and configuration quantity as the goal. According to the standard of parameter identification
accuracy and configuration quantity of distribution network,the optimal configuration scheme of synchronous
measurement device with the minimum objective function was obtained. The experimental results show that the
identification mean error of node voltage is small,which is controlled between 0.10% and 0.26%,which can
significantly reduce the parameter identification error of the research object.
Key words: parameter;identification accuracy;distribution network;synchronous measurement device;
optimal configuration